Home  /  ELR and CBCT  / 

Split Core Balanced Current Transformer (CBCT – ZSC Zero Sequence Current Transformers)

Sizing Guide

Wishlist Please, enable Wishlist.
Category: ELR and CBCT
Share: Facebook Twitter Tumblr Linkedin Whatsapp

You may also like

  • Type A Smart Earth Leakage Relay with Harmonic Filter

    Type A Smart Earth Leakage Relay with Harmonic Filter

  • PTC Panel Heaters

    PTC Panel Heaters

  • Axial Fan 280 X 280 mm 220V

    Axial Fan 280 X 280 mm 220V

  • Fuse Holder ( Cylindrical Type )

    Fuse Holder ( Cylindrical Type )

  • Axial Fan 120X120mm 220V

    Axial Fan 120X120mm 220V

  • Core Balanced Current Transformer (CBCT - ZSC Zero Sequence Current Transformers)

    Core Balanced Current Transformer (CBCT - ZSC Zero Sequence Current Transformers)

Description
Shipping & delivery

Split Core CBCT (Core Balance Current Transformer)

Flexible Earth Leakage Monitoring for Existing Installations

The HS Grup Split Core CBCT Series is specifically designed for earth leakage current detection in existing electrical installations where disconnecting cables or busbars is difficult or impractical. The split-core design allows the transformer to be opened and installed around existing conductors without interrupting power or dismantling the system.

When used with Earth Leakage Relays (ELR), the Split Core CBCT provides accurate residual current monitoring and reliable earth fault protection for industrial and commercial applications.


Key Features

  • Split-core design for easy retrofit installation
  • No need to disconnect existing cables or busbars
  • High sensitivity earth leakage current detection
  • Compatible with Earth Leakage Relays (ELR)
  • Suitable for large busbar and cable systems
  • Robust industrial construction
  • Easy opening and closing mechanism
  • Reliable performance in demanding environments
  • Ideal for panel upgrades and maintenance projects

Applications

  • Existing Electrical Switchboards
  • MCC Panels
  • Power Distribution Systems
  • Industrial Plants
  • Generator Protection Systems
  • Transformer Protection
  • Data Centers
  • Commercial Buildings
  • Renewable Energy Systems
  • Solar Power Plants
  • Retrofit Earth Leakage Protection Projects

Technical Specifications

Parameter Value
Product Type Split Core Core Balance Current Transformer
Frequency 50/60 Hz
Ratio 1000/1
Surge Voltage Resistance 3 kV
Test Voltage 3 kV AC / 1 Minute
Insulation Resistance DC 500V / 100 MΩ
Protection Class IP20
Operating Temperature -45°C to +55°C
Ambient Temperature -20°C to +55°C
Standards IEC 60947-2

Available Models

KCBCT-1-36-10

Specification Value
Opening Size 360 × 100 mm
Rated Current 5000 A
Type Split Core

KCBCT-1-50-10

Specification Value
Opening Size 500 × 100 mm
Rated Current 5500 A
Type Split Core

KCBCT-1-20-20

Specification Value
Opening Size 200 × 200 mm
Type Split Core

KCBCT-1-30-30

Specification Value
Opening Size 300 × 300 mm
Type Split Core

How Split Core CBCT Works

The Split Core CBCT continuously monitors the vector sum of all phase conductors and neutral passing through the core.

Under normal conditions, the sum of currents is zero. When an earth leakage fault occurs, the resulting imbalance creates a residual current signal that is detected by the CBCT and transmitted to the connected Earth Leakage Relay (ELR), enabling alarm indication or circuit disconnection.


Installation Advantages

Fast Retrofit Installation

Unlike conventional closed-core CBCTs, split-core models can be installed around existing cables and busbars without disconnecting conductors.

Reduced Downtime

Installation can often be completed without shutting down critical equipment, reducing maintenance costs and operational interruptions.

Ideal for Large Busbars

The large rectangular opening accommodates high-current busbar systems commonly found in industrial and commercial switchboards.


Compatible Products

Fully compatible with:

  • HS Grup KAR-1 Earth Leakage Relay
  • Earth Leakage Protection Systems
  • Residual Current Monitoring Systems
  • Generator Protection Panels
  • Main Distribution Boards (MDB)
  • Motor Control Centers (MCC)

Benefits

✓ Easy installation on existing systems

✓ No cable disconnection required

✓ Reliable earth leakage detection

✓ Suitable for large busbars and cable bundles

✓ Reduced installation time

✓ Increased system safety

✓ Industrial-grade performance

✓ Long operational life

Related products

Analog Earth Leakage Relay
Read more Quick View
ELR and CBCT

Analog Earth Leakage Relay

Digital Earth Leakage Relay
Read more Quick View
ELR and CBCT

Digital Earth Leakage Relay

Core Balanced Current Transformer (CBCT - ZSC Zero Sequence Current Transformers)
Read more Quick View
ELR and CBCT

Core Balanced Current Transformer (CBCT – ZSC Zero Sequence Current Transformers)

Type A Smart Earth Leakage Relay with Harmonic Filter
Read more Quick View
ELR and CBCT

Type A Smart Earth Leakage Relay with Harmonic Filter

Type A Smart Earth Leakage Rel...

Core Balanced Current Transfor...

HS Grup is a trusted manufacturer of industrial electrical materials, offering reliable and innovative solutions for a wide range of applications. With a strong focus on quality, safety, and customer satisfaction

Useful Links

  • Home
  • About us
  • Products
  • CATALOG
  • Certificates
  • Contact us
  • English
  • Türkçe

Products

  • Current Transformers
  • Metal Enclosures
  • Terminal Block

Contact Us

Email = info@hsgrup.com.tr
Phone = +90 553 122 89 38
Mon – Fri 9:00 AM to 6:30 PM SUNDAY – Closed
Address: A: HALİL RIFAT PAŞA MAH. YÜZER HAVUZ SK. PERPA TİC MER B BLOK NO: 543 ŞİŞLİ / İSTANBUL

Facebook Instagram Linkedin

Copyright © 2025 HS Group  All rights reserved.